Photovoltaic wire (PV) is mainly used for the transmission of DC power generated by the photovoltaic panels and widely used for the interconnection of photovoltaic modules and DC combiner boxes. It is also used for the rest connection of the photovoltaic system or similar power generation system. Suitable for fixed installation outdoors, indoors, for direct burial, in cable tray and cable conduits.
STANDARDS:
UL 4703 Standard for photovoltaic wire
UL 44 Standard for Thermoset-Insulated Wires and Cables
UL 854 Standard for Service-Entrance Cables
Conductor: |
- Bare or tinned copper conductor, Class 2 as per IEC 60228
-Flexible bare or tinned copper conductor, Class 5 & Class 6 as per IEC 60228
-Aluminium or aluminium alloy (8030), class 2 as per IEC60228
|
Insulation: |
XLPE |
Sheath: |
XLPE |
1 x AWG18 ~ 1x2000KCMIL
Insulation: white (natural)
Sheath: black, red, blue, etc.
Rated Voltage U |
600V, 1000V or 2000V AC,
Rating 90° C Wet or Dry Operation, Rating 105° C Dry Operation
|
Maximum permissible conductor operating temperature |
+105° C Dry Operation |
Operating ambient temp. range |
- 40℃/+90℃ |
Long Term Insulation Resistance |
meet Long Term Insulation Resistance Test in water 90℃ |
Long Term Capacitance: |
meet Long Term Capacitance Test in water 90℃ |
Flame retardant: |
meet Flame Test VW-1, FV-1 and FT-2 |
Resistance to Low temperature |
Meet Cold Bend Test at -40°C temperature
Meet Cold Impact Test at -40°C temperature
|
UV resistant |
Good |
Direct burial |
Service Entrance Cable per UL 854:
•Section 23 Impact Test
•Section 24 Crushing Test
|
Minimum bending for installation |
4xD(D is cable overall diameter) |