• information
APPLICATION:
The MV power cables have the capacity of both power transmission and optical fiber communication. Suitable for the composite system of power transmission and distribution and optical fiber communication with rated voltage of 3.6/6 – 26/35kV
STANDARD:
GB/T12706; IEC60502-2
Or as per other standards request by customer

CONSTRUCTION:

Conductor:

Copper, or aluminum, or aluminium alloy 8030, as per IEC60228 Class 2

Conductor screen:

Semi-conducting compound

Insulation:

XLPE or TR-XLPE or HEPR

Insulation screen:

Semi-conducting compound

Metallic screen:

-Copper tape screen (CTS), or
- Copper wire screen plus one equalizing copper tape open counter-helix (CWS)

Optical fiber cores

To be placed in the filler interspaces for three core cables, or between the copper wires screen for single core cable

Filler:

Non-hygroscopic polypropylene (PP) yarn

Binder tape

Non-hygroscopic tape

Inner sheath(for armoured cable):

Extruded PVC, or PE, or LSOH

Armour (for armoured cable):

-Single core: non-magnetic stainless steel wire(SUSWA), or non-magnetic stainless steel tape(DSUSTA), or non-magnetic round aluminium wire (AWA);
-Three-core: galvanized steel tape(DSTA), or galvanized steel wire(SWA);

Outersheath:

Extruded PVC, or PE, or LSOH

RATED VOLTAGE, RANGE OF SIZES:


Rated Voltage
Uo/U (Um)


Number of cores

Range of Sizes

Copper conductor

Aluminum conductor


3.6/6kV (7.2kV)
6/10kV (12kV)
8.7/15kV (17.5kV)


Single core

16mm2~1000mm2

25mm2~1200mm2

Three core

16mm2~500mm2

25mm2~500mm2


12/20kV (24kV)
18/30kV (36kV)
26/35kV (40.5kV)


Single core

35mm2~1000mm2

35mm2~1200mm2

Three core

35mm2~500mm2

35mm2~500mm2

CORE IDENTIFICATION:
Single core:by natural colour of insulation
Three- core:by coloured plastic tape of yellow, green and red, or by printing number 1, 2, 3, or as per customer’s requirement
SHEATH COLOR:
black, or as per customer’s requirement
USAGE CHARACTERISTICS:











Max. conductor temp. in service
90℃

Max. short circuit temp. (5s)
250℃

Min. installation
temperature
0℃

Flame-retardant
IEC600332-1-2

Min. bending radius when laying
-Single core: 20 (×D)
-Three core: 15 (×D)

SPECIAL FEATURES ON REQUEST:










>






Flame retardant
IEC60332-3
(Cat. A,B or C)

Low smoke
IEC 61034

Halogen free IEC60754

Anti-termite

Anti-rodent

UV resistant

Water blocking
(longitudinally and radial)

Feedback form contact with us
Product Catalog