This aluminium alloy (8030) conductor XLPE insulated power cables are mainly used in the power distribution system of variable kind of residential buildings, industry and commercial buildings. They are suitable for fixed installation and laying indoor, cable tray, in tunnel, pipe, cable trench and loose soil, the cable cannot bear external mechanical force.
STANDARDS:
Q/320481SS364, NB/T 42051, GB/T 31840, GB/T12706.1, IEC60502-1.
Conductor: Stranded circular compacted aluminium, class 2
Insulation: Cross-linked Polyethylene(XLPE)
Filler and Binder tape for multi-core assembly
Outer sheath: Polyvinyl chloride(PVC), or flame retardant PVC
WDZ*-YJLHY-0.6/1kV:
Conductor: Stranded circular compacted aluminium, class 2
Insulation: Cross-linked Polyethylene(XLPE)
Filler and binder tape for multi-core assembly
Outer sheath: low smoke halogen free flame retardant polyolefin(LSZH)
- Single core:10mm2~630mm2
- Two-core:10mm2~400mm2
- Three-core: 10mm2~400mm2
- Four-core(including 3+1): 10mm2~400mm2
- Five-core(including 3+2, 4+1): 16mm2~400mm2
No. of core |
Core identification in China |
Core identification as per IEC60445, BS7671 |
|
With earth core |
Without earth core |
||
Single core |
yellow |
Brown (or natural color) |
Brown (or natural color) |
Two-core |
red, blue |
- |
Brown, blue |
Three-core |
yellow, green, red |
Green-yellow, brown, blue |
Brown, black, gray |
Four-core |
yellow, green, red, blue |
Green-yellow, brown, black, gray |
Brown, black, gray, blue |
Five-core |
yellow, green, red, blue, yellow/green |
Green-yellow, brown, black, gray, blue |
Brown, black, gray, blue, black |
Note: other core identification colour is available upon request.
Black, or as per order.
MAIN TECHNICAL PARAMETER:
Voltage range: 0.6/1kV
Maximum continuous operating temperature: 90℃
Maximum short circuit temperature(maximum duration 5s): 250℃
Minimum environment temperature for installation: 0℃
Minimum bending radius of cable: 15×O.D.(multi-core cable), 20×O.D.(multi-core cable)
Flame retardant to IEC60332-1
OPTIONAL CHARACTERISTICS ON REQUEST:
Flame retardant (ZC, ZB, ZA): Acc. to IEC60332-3, GB/T18380, Category A, B, C
Low smoke halogen free: IEC61034, GB/T17651, IEC60754,GBT/17650 (for LSZH cable)
Anti-termite/anti-rodent
Low temperature use
UV resistant