• information
APPLICATION:
These LSZH double insulated building cable are suitable for fixed wiring and installation, indoor and outdoor, in surface mounted or embedded conduits, or similar closed systems,
These cables are designed for fire extinguishing system, emergency system, lighting system, power transmission and distribution system etc. across for residential areas, commercial building and public building areas, industrial plant. The design lifetime of cable shall be 70 years.

STANDARDS:
Basic design to Q/320481SS472, IEC60228, IEC60332-1 & IEC60332-3, GB/T17651/IEC61034, GB/T17650/IEC60754.

CONSTRUCTION:
WDZ*GYJS(F)Y
Conductor: solid or stranded circular copper wire, class 1&2 to IEC60228
Insulation-inner layer: irradiation XLPE compound
Insulation-outer layer: irradiation XLPO insulation
Filler
Binder tape covering
Outer sheath: extruded low smoke halogen free polyolefin (LSZH)

NUMBER OF CORES & CONDCUCTOR SIZES
Single core:1.5mm2~400mm2
Two- core: 1.5mm2~400mm2
Three-core:1.5mm2~400mm2
Four-core(including 3+1): 1.5mm2~400mm2
Five-core(including 4+1 and 3+2):1.5mm2~400mm2

CORE INDENTIFICATION
Inner layer XLPE: natural colour
Outer layer XLPO: see table below.

No. of core

Core identification in China

Core identification as per IEC60445, BS7671

With earth core

Without earth core

Two-core

red, blue

-

Brown, blue

Three-core

yellow, green, red

Green-yellow, brown, blue

Brown, black, gray

Four-core

yellow, green, red, blue

Green-yellow, brown, black, gray

Brown, black, gray, blue

Five-core

yellow, green, red, blue, yellow/green

Green-yellow, brown, black, gray, blue

Brown, black, gray, blue, black

SHEATH COLOUR
Orange, or other colour upon request

MAIN TECHNICAL PARAMETER
Rated voltage: 0.6/1kV
Maximum continuous operating temperature: 90℃
Maximum short circuit temperature(maximum duration 5s): 250℃
Minimum environment temperature for installation: 0℃
Cable operating ambient temperature scope: -15℃ ~ 55℃
Minimum bending radius of cable: 15×O.D.(multi-core cable), 20×O.D.(multi-core cable)

OPTIONAL CHARACTERISTICS ON REQUEST
Flame retardant (*): Acc. to IEC60332-3-24(ZC), IEC60332-3-23(ZB), IEC60332-3-22(ZA)
Low smoke halogen free: GB/T 17651/IEC61034, GB/T 17650/IEC60754 (for LSZH cable)
Anti-termite/anti-rodent
Low temperature use
UV resistant
Feedback form contact with us
Product Catalog